Meter monitoring

Meter monitoring ensures that EnergyControl constantly receives up-to-date meter readings. This enables any failures or problems with data transmission to be detected at an early stage.

Each meter reading is assigned a status:

Status Value Meaning
Not OK – Simulated value -3 The meter reading is simulated.
Not OK – Bus failure -2 No communication with the meter.
Not OK – Reading error -1 Hardware meter reports an error during reading.
OK – Value not plausible 0 Data is present, but the value is not plausible.
OK – value plausible 1 Data available and the value is plausible.

Monitoring on the controller

The counter values are checked for plausibility on the controller. The following monitoring functions are available:

  • No change in value: If the counter does not change its value within a configurable time period, an alarm is triggered.
  • Negative value change: If the read counter value is less than the last value read, an alarm is triggered.
  • Excessive value change: If the read meter value is greater than the last read value plus a configurable offset, an alarm is triggered.
  • Change in the wrong tariff: If the meter value changes to the wrong tariff, an alarm is triggered. This is only relevant if the meters are read in dual-tariff mode.

Monitoring on the server

The system checks whether meter readings have been received within a defined time period.

  • If no meter readings are received within 24 hours, an alarm is triggered.
  • If no change in the meter readings is detected within 24 hours, an alarm is also triggered.

When an alarm is triggered, a ticket is automatically created for our support team. The support team investigates the cause and processes the ticket without the customer needing to take any action.